蜜乳中文无码AV_中文字幕精品在线一区二区_国产主播极品尤物午夜福利_亚洲最新黄色性爱视频_爱爱视频网站日本亚洲_精品亚洲V热蜜乳_琪琪高清无码一区_狠狠操屄网_成人国产精品无码999999_中文字幕XXX高清免费在线视频_a在线观看av_黄色的网站在线观看无码_WWW,黄片,COM_大肉棒插入久久_丝袜淫乱五月天

您好,歡迎訪問安科瑞電氣股份有限公司! 咨詢熱線:13774430992

技術(shù)文章/ TECHNICAL ARTICLES

我的位置:首頁  >  技術(shù)文章  >  Application of ACREL Medical IT Insulation Device

Application of ACREL Medical IT Insulation Device

更新時(shí)間:2021-02-25      瀏覽次數(shù):1171

1、Background

Electric shock and system fault caused by power distribution system are mostly caused by the grounding fault of equipment line. Grounding fault will directly bring the harm of power supply interruption; when the earth fault leakage is serious, it will even burn electrical equipment or lines, causing irreparable loss.

 

In Medical places, especially those life-threatening class 2 medical places, patients in surgery or anesthesia state, without self-behavior ability, small leakage current can lead to electric shock death of patients. Therefore, the electrical design of this special place should be carried out strictly in accordance with the relevant national standards and specifications.

IT power distribution system (also known as isolated power supply system or ungrounded system) has very small leakage current to ground due to its neutral point ungrounded. When the first insulation fault occurs, the power supply of the equipment will not be affected. So the system can continue to operate. The insulation monitoring device installed in the system can detect the fault in time and send out the corresponding fault warning, prompting the relevant personnel to remove the fault at the appropriate time. For the operation room, intensive care unit and other medical places with high requirements for power supply continuity and safety, local IT system power supply can ensure the security and reliability of power supply for important loads.

 

2、Project Information

Ky Anh's Medical Center, a medical facility in Vietnam, has introduced five sets of insulation monitoring products for operating rooms to improve its medical facilities.

3、Description of four sets of medical IT products

The medical IT system is mainly used in important Class 2 medical locations such as operating room, ICU/CCU intensive care unit, providing safe, reliable and continuous power distribution for the important equipment at these locations. Medical insulation monitoring and fault locating device is developed by the many years’ design experience of the Acrel Electric in electric power meter industry, according to the special requirements of the insulation monitoring and fault locating of the power distribution system in Class 2 medical locations. The products can realize the real-time monitoring of insulation, load and temperature of isolation transformer in IT system, and have the functions of system insulation fault loop positioning and centralized monitoring by multiple pieces of systems. Products conform to the provisions of enterprise standard Q31/29C013-2016 IT System Insulation Monitoring Instrument.

Medical IT system insulation monitoring (four-piece set) include AITR series medical isolation transformer, AIM-M10 medical inligent insulation monitoring instrument, AKH-0.66P26 current transformer, and AID series(AID10、AID130、AID150) centralized alarm and display instrument, which are shown in Table 1 

4、Typical application of isolated power supply system